Daycool Academy
Week 5: Electrical & Controls
Master the fundamentals of HVAC electrical systems and control technologies
This Week's Learning Objectives
Electrical Safety
Master lockout/tagout procedures, proper PPE usage, and voltage testing protocols to ensure safe work practices on every job site.
Wiring Diagrams
Read and interpret ladder diagrams, schematic drawings, and pictorial diagrams used in residential and commercial HVAC systems.
Circuit Fundamentals
Understand the difference between low-voltage control circuits and high-voltage power circuits, including proper wire sizing and connections.
Control Systems
Install, configure, and troubleshoot thermostats including our SmartFeather product line for optimal customer comfort and system efficiency.
Electrical Safety: Your Life Depends On It
Core Safety Protocols
Electricity is invisible, silent, and potentially lethal. Every HVAC technician must treat electrical work with absolute respect and follow established safety procedures without exception. One moment of carelessness can result in serious injury or death.
Before touching any electrical component, you must verify the power is off using a properly rated voltage tester. Never assume a circuit is de-energized based on switch position alone. Always follow the lockout/tagout procedure to prevent accidental energization while you're working.
Wear appropriate personal protective equipment including insulated gloves rated for the voltage you're working with, safety glasses, and non-conductive footwear. Remove jewelry and avoid working in wet conditions. If you're unsure about any electrical task, stop and ask a senior technician for guidance.

Critical Safety Rules
  1. Test before touch - verify power is off
  1. Use lockout/tagout on all disconnects
  1. Wear properly rated PPE always
  1. Keep one hand in pocket when testing live circuits
  1. Never bypass safety devices or fuses
  1. Work with a partner on high-voltage tasks
Understanding Lockout/Tagout Procedures
01
Notify Affected Parties
Inform the customer, building manager, or facility occupants that you'll be shutting down power to perform maintenance work.
02
Locate & Identify Energy Sources
Find all disconnects, breakers, and power sources that supply the equipment. Check wiring diagrams if multiple circuits are involved.
03
Shut Down Equipment Properly
Turn off the system using normal shutdown procedures before disconnecting power to prevent damage to components.
04
Isolate Energy Sources
Open disconnects, turn off breakers, and remove fuses as appropriate. Multiple lock points may exist on commercial equipment.
05
Apply Locks & Tags
Place your personal lock on each disconnect with a danger tag showing your name, date, and reason for lockout.
06
Verify Zero Energy State
Use your voltage tester to confirm no voltage is present at the equipment before beginning work. Test all phases and ground.
Reading Wiring Diagrams Like a Pro
Three Types of Diagrams
Ladder diagrams are the most common in HVAC. They show the electrical circuit arranged like a ladder, with power lines on the sides and components arranged as horizontal rungs. Each rung represents a complete circuit path from line to neutral or ground.
Schematic diagrams use standardized symbols to show electrical relationships between components without regard to their physical location. These are ideal for understanding circuit operation and troubleshooting logic problems.
Pictorial diagrams show components as they physically appear and their actual location in the unit. These are helpful for identifying parts and understanding wire routing during installation.
Essential Diagram Symbols
  • Transformer: Two parallel coils stepping voltage up or down
  • Contactor/Relay: Box with coil and multiple switches
  • Capacitor: Two parallel lines representing stored charge
  • Thermostat: Temperature-activated switch contacts
  • Compressor: Circle with motor windings shown inside
  • Fan Motor: Circle with "M" and arrow indicating rotation
  • Switch: Break in line with actuating mechanism

Practice reading diagrams daily. Start by identifying the power source, then trace each circuit from hot to neutral. Color-code wires mentally as you go: red for hot, white for common, green for ground. Over time, circuit patterns will become instantly recognizable.
Low-Voltage Control Circuits: The Brain of the System
24V AC Standard
Nearly all residential HVAC systems use 24-volt alternating current for control circuits. This voltage is safe to work with and allows for long wire runs without voltage drop issues. The transformer steps down 120V or 240V line voltage to 24V for the control circuit.
The 24V circuit powers the thermostat, zone controls, safety switches, and the coils of contactors and relays. When you close a thermostat contact, you're completing a 24V circuit that energizes a relay, which then switches the high-voltage power to motors and compressors.
Wire Color Standards
While colors aren't always followed perfectly, standard wiring uses these conventions: R (red) carries 24V hot from the transformer. C (blue/black) is the common return. W (white) controls heating. Y (yellow) controls cooling. G (green) controls the fan. O/B (orange/blue) switches between heating and cooling modes on heat pumps.
Always verify wire function with a meter rather than relying solely on color, especially in older installations or after repairs by other technicians.
Troubleshooting Low-Voltage Issues
Most HVAC service calls involve low-voltage control problems rather than high-voltage failures. Start by checking transformer output voltage—it should read 24-28V AC. Low voltage indicates a weak transformer or short circuit somewhere in the wiring.
Use your meter to trace circuits systematically. Check voltage at the thermostat, then at each component. A blown fuse in the control circuit usually indicates a short—find and fix the short before replacing the fuse or you'll blow it again immediately.
High-Voltage Power Circuits: Handle With Respect
Understanding Power Distribution
High-voltage circuits carry the power needed to run compressors, fan motors, and electric heaters. In residential systems, this is typically 208V or 240V single-phase power. Commercial systems may use 480V three-phase power, which is significantly more dangerous.
Single-phase power uses two hot legs (L1 and L2) plus ground. Each leg measures 120V to ground and 240V between them. Most residential air conditioners and heat pumps run on 240V single-phase. The compressor and condenser fan operate on this voltage.
Three-phase power is more efficient for large motors and provides smoother operation. It uses three hot legs (L1, L2, L3) that are 120 degrees out of phase. Commercial rooftop units typically use 208V or 480V three-phase. Always check equipment nameplates for voltage requirements before connecting power.
Wire sizing is critical for high-voltage circuits. Undersized wires create resistance, generate heat, and can cause fires. The National Electrical Code specifies minimum wire gauges based on amperage and run length. When in doubt, go one size larger—the cost difference is minimal and the safety margin is worth it.

⚠️ High-Voltage Safety
Never work on energized high-voltage circuits. Always disconnect power at the breaker or disconnect and verify with a meter before touching wires.
High voltage can arc several inches through air and jump across gaps, creating plasma that reaches thousands of degrees.
Contactors and Relays: Electrical Muscle
Low-Voltage Control Signal
The thermostat sends a 24V signal when calling for cooling or heating. This small current flows through the coil of a contactor or relay.
Electromagnetic Coil Energizes
The 24V current creates a magnetic field in the coil, which pulls a metal armature containing the contact assembly.
Contacts Close
The armature movement closes heavy-duty contacts that complete the high-voltage circuit, allowing full power to flow to compressors and motors.
Equipment Operates
With contacts closed, 240V power energizes the compressor and condenser fan motor. The system runs until the thermostat opens the 24V circuit.

Contactors handle high amperage loads like compressors and use silver or silver alloy contacts rated for tens of thousands of operations. Relays switch smaller loads like fan motors and typically have gold-plated contacts for low-resistance switching. Both operate on the same electromagnetic principle—a small control current switches a much larger power circuit.
Wire Sizing and Ampacity
Understanding Wire Gauge
Wire size is measured using the American Wire Gauge (AWG) system, where smaller numbers indicate larger wire diameters. A 10 AWG wire has a larger cross-sectional area than 14 AWG and can safely carry more current.
Each wire size has a maximum ampacity—the amount of current it can safely carry without overheating. The ampacity depends on the wire material (copper vs. aluminum), insulation type, ambient temperature, and whether wires are bundled together or run individually.
For HVAC applications, copper wire is standard. Common residential circuit wire sizes: 14 AWG carries up to 15 amps, 12 AWG carries up to 20 amps, 10 AWG carries up to 30 amps, and 8 AWG carries up to 40 amps. Always check the equipment nameplate for minimum circuit ampacity (MCA) and maximum overcurrent protection (MOP).
Calculating Voltage Drop
Long wire runs cause voltage drop due to wire resistance. Excessive voltage drop reduces equipment efficiency and can damage motors by causing them to draw higher amperage while producing less power.
Voltage drop should not exceed 3% for branch circuits and 5% total from service entrance to equipment. For a 240V system, 3% equals 7.2 volts. If you measure 233V or less at the equipment, the wire run is too long for the gauge used.
To reduce voltage drop, increase wire size or shorten the run. Use online voltage drop calculators or the formula: VD = (2 × K × I × D) / CM, where K is the resistance constant, I is current, D is distance, and CM is circular mils of wire area.
Thermostats: The Command Center
The thermostat is the user interface between the customer and their HVAC system. It senses room temperature, compares it to the setpoint, and activates heating or cooling as needed. Modern thermostats have evolved from simple mechanical switches to sophisticated digital computers.
1
Mechanical (1950s-1980s)
Used a bimetallic coil that expanded and contracted with temperature changes, physically opening and closing switch contacts. Simple and reliable but limited in features and accuracy (±2-3°F).
2
Digital Programmable (1980s-2000s)
Incorporated electronic temperature sensors and digital displays. Allowed programmed schedules for different times and days, improving comfort and energy efficiency with better accuracy (±0.5°F).
3
Smart Thermostats (2010s-Present)
WiFi-enabled with smartphone apps, learning algorithms, remote sensors, and integration with home automation systems. Provide usage reports, weather prediction, and voice control capabilities.
Basic Thermostat Operation
Heating Mode
When room temperature falls below the setpoint, the thermostat closes the heating contact, completing the circuit from R to W terminals. This 24V signal energizes the gas valve (for furnaces) or heat pump reversing valve (for heat pumps).
The system monitors temperature continuously. Once the setpoint is reached, the thermostat opens the W contact, stopping the heating cycle. Most thermostats include a differential or "swing" of 1-2 degrees to prevent rapid cycling that would wear out equipment.
Many thermostats have a G (fan) terminal that can run independently. The fan can operate continuously or auto mode where it runs only when heating or cooling is active.
Cooling Mode
When room temperature rises above the setpoint, the thermostat closes the cooling contact, completing the circuit from R to Y terminals. This 24V signal energizes the contactor coil, which closes the high-voltage contacts to the compressor and condenser fan.
Air conditioning systems require a few minutes between cycles to allow refrigerant pressures to equalize. Quality thermostats include a time-delay feature preventing restart for 3-5 minutes after shutdown, protecting the compressor from damage.
On heat pump systems, the O (or B) terminal controls the reversing valve, switching between heating and cooling modes by changing refrigerant flow direction.
Introducing SmartFeather: The Daycool Advantage
Our Premium Smart Thermostat
SmartFeather represents Daycool's commitment to cutting-edge comfort technology. This premium thermostat combines intuitive design with advanced features that keep customers comfortable while reducing energy costs by up to 23% compared to basic programmable models.
As Daycool technicians, you'll install, configure, and support SmartFeather systems. Understanding its capabilities allows you to position it as an upgrade option that benefits both the customer and your commission.

Installation Tips: SmartFeather requires a C-wire for power. Always check existing wiring before quoting installation. Add-a-wire kits are available if needed.
Mobile App Control
Full system control from anywhere with iOS or Android apps. Customers can adjust temperature, view energy usage, and receive maintenance alerts remotely.
Learning Algorithm
Adapts to household schedules automatically after one week of observation. Creates optimal comfort schedules without manual programming required.
Weather Integration
Adjusts heating and cooling based on forecast data, pre-conditioning the home for maximum efficiency and comfort during temperature swings.
Energy Reports
Detailed monthly usage analytics help customers understand their energy consumption patterns and identify opportunities for additional savings.
SmartFeather Installation Process
Kill Power & Photograph Old Thermostat
Turn off power at the breaker and verify it's off with your meter. Take clear photos of the existing thermostat wiring before removing any wires—this documentation is invaluable if questions arise later.
Label and Remove Wires
Use the included wire labels to mark each wire with its terminal letter (R, W, Y, G, C, etc.). Carefully remove wires from the old thermostat and remove the old wall plate. Check the wall for any damage that needs patching.
Mount SmartFeather Base
Level the new wall plate and mark screw holes. If the old holes don't align, use drywall anchors for a solid mount. Route wires through the center opening and secure the base plate firmly to the wall.
Connect Wires to Terminals
Insert each labeled wire into its corresponding terminal on the SmartFeather base. The push-in connectors hold wires securely—tug gently to verify. Ensure the C-wire is connected for continuous power.
Attach Display & Power Up
Snap the SmartFeather display onto the base plate—it will click into place. Restore power at the breaker. The welcome screen should appear within 10 seconds. If not, verify wiring connections and power at the transformer.
Configure WiFi & System Settings
Follow the on-screen setup wizard to connect SmartFeather to the customer's WiFi network. Configure system type (heat pump, gas furnace, etc.), number of stages, and reversing valve energization. Test each mode before leaving.
SmartFeather Features That Sell Systems
Geofencing
Automatically adjusts temperature based on whether anyone is home using smartphone location data. The system switches to an eco-friendly setback when the last person leaves and begins conditioning 30 minutes before the first person arrives. Customers love the convenience and energy savings without any manual adjustments.
Room Sensors
SmartFeather supports up to 4 wireless room sensors that measure temperature and occupancy in different areas. The system averages readings or prioritizes occupied rooms, eliminating hot and cold spots. Perfect for homes with challenging layouts or bedrooms far from the main thermostat.
Filter Reminders
Tracks runtime hours and notifies customers when it's time to change the air filter. Sends push notifications to their phone and displays alerts on the thermostat screen. Clean filters improve efficiency, indoor air quality, and extend equipment life—a win for everyone.
Vacation Mode
Customers can set extended away periods through the app, and SmartFeather maintains minimal heating or cooling to prevent frozen pipes or excessive humidity. The system automatically returns to the normal schedule when vacation ends, ensuring comfort upon arrival home.
Common Thermostat Wiring Mistakes
Thermostat wiring errors are among the most common service calls for HVAC technicians. Many mistakes result from confusion about wire functions, mismatched equipment, or simply mixing up similar-looking terminals. Learning to recognize and avoid these errors will save you callback headaches and build your professional reputation.
1
Reversing R and C Wires
This is the deadliest mistake—connecting 24V hot (R) to the common terminal (C) creates a direct short circuit that instantly blows the transformer fuse. Always double-check: R carries power from the transformer, C returns to the transformer. Some systems use Rh and Rc for separate heating and cooling transformers.
2
Connecting Line Voltage to Low-Voltage Terminals
Occasionally installers accidentally connect 120V or 240V wires to thermostat terminals designed for 24V. This destroys the thermostat instantly and can create a fire hazard. Always verify voltage with your meter before making connections. Line voltage thermostats exist for baseboard heaters but are completely different devices.
3
Forgetting the C-Wire
Many older thermostats didn't require a common wire, but modern smart thermostats need continuous power to maintain WiFi, displays, and processors. Without a C-wire, batteries drain quickly or the thermostat "steals" power through other terminals, causing phantom calls for heating or cooling. Install a C-wire or use an add-a-wire kit.
4
Mixing Up O and B on Heat Pumps
Heat pump reversing valves are energized in either cooling mode (O terminal) or heating mode (B terminal) depending on manufacturer. Installing a thermostat configured for O on a B-type system means the heat pump operates backward—heating when you want cooling. Check equipment specs or test before calling it done.
More Wiring Mistakes to Avoid
Bare Wire Touching Metal Base
Stripped wire ends must be fully inserted into terminals with no exposed copper visible. Bare wire contacting the thermostat base plate creates shorts that blow fuses and cause intermittent operation. Trim wires carefully and double-check every connection.
Using Wrong Wire Gauge
Thermostat wire should be 18 AWG minimum for runs up to 100 feet. Longer runs or higher-amp accessories may require 16 AWG. Using doorbell wire or telephone wire causes voltage drop, erratic operation, and early component failure. Always use proper thermostat cable.
Sharing Terminals
Each wire should have its own terminal. Never double-up wires by twisting them together and jamming both into one terminal. This creates poor connections, voltage drops, and intermittent problems that are difficult to diagnose. If you need to split a circuit, use a proper wire junction with terminal blocks.
Assuming Colors Match Functions
While color conventions exist, previous installers don't always follow them. Never assume a yellow wire goes to Y without testing. Trace each wire back to the equipment or use your meter to verify which terminal each wire connects to before labeling and reconnecting.
Essential Electrical Tools for HVAC Techs
Digital Multimeter (DMM)
Your most important diagnostic tool. A quality DMM measures AC/DC voltage, current, resistance, and continuity. For HVAC work, you need a meter rated for at least CAT III 600V safety category to handle the voltages you'll encounter.
Essential functions: Voltage testing verifies power at disconnects, transformers, and components. Resistance testing checks heater elements, motor windings, and wire integrity. Continuity testing identifies open circuits, blown fuses, and broken wires. Diode testing checks capacitors and solid-state controls.
True-RMS meters provide accurate readings on the variable-frequency drives found in modern equipment. Auto-ranging simplifies operation by automatically selecting the correct scale. Invest in a quality meter with a lifetime warranty—cheap meters give inaccurate readings and create safety risks.
Clamp-On Ammeter
Measures current flow without breaking the circuit by sensing the magnetic field around a wire. Essential for checking compressor amp draw, verifying proper motor operation, and detecting shorts or overloads.
How to use: Open the clamp jaws and place them around a single conductor—clamping around both wires of a circuit gives zero reading because currents cancel. The meter displays amperage flowing through that wire. Compare readings to equipment nameplate ratings.
Modern clamp meters include multimeter functions, making them versatile diagnostic tools. True-RMS clamp meters accurately read variable-frequency drive outputs. Some include in-rush current modes for measuring compressor starting amps, helpful for diagnosing hard-start problems.
More Tools in Your Electrical Arsenal
Non-Contact Voltage Tester
A safety device that detects AC voltage without touching wires. Beeps and lights up when brought near energized circuits. Use it to verify power is off before opening equipment panels. Not precise enough for diagnosis but perfect for quick safety checks. Battery-operated, so test the tester before each use.
Wire Strippers
Purpose-built wire strippers have sized holes that remove insulation without nicking the conductor. Damaged wires develop high resistance and can fail. Avoid using knife blades or side-cutting pliers that score the copper. Automatic wire strippers speed up the job and provide consistent results. Invest in quality—you'll strip hundreds of wires per month.
Capacitor Tester
Measures capacitance in microfarads (µF) and checks for shorts or opens. Bad capacitors are a leading cause of compressor and fan motor failure. Test capacitors under load for accuracy—some meters have this feature built-in. Always discharge capacitors using an insulated screwdriver across terminals before testing or removing. Stored charge can deliver a painful or dangerous shock.
Megohmmeter (Megger)
Tests insulation resistance using high DC voltage (typically 500-1000V) to detect breakdown in motor windings, wire insulation, or compressor integrity. Readings below 1 megohm indicate insulation failure and risk of ground faults. Never megger solid-state controls or circuit boards—you'll destroy them. Disconnect all electronics before testing. Advanced diagnostic tool for electrical troubleshooting.
Using Your Multimeter: Voltage Testing
01
Select Voltage Mode & Range
Turn the dial to AC voltage (V~) for most HVAC measurements. If your meter isn't auto-ranging, select a scale higher than expected voltage. For 240V circuits, use the 600V scale. For 24V circuits, use 200V scale.
02
Insert Probes into Meter
Insert the black probe into the COM (common) jack and the red probe into the V/Ω jack. Never insert probes into the Amp jack for voltage testing—you'll create a short circuit and blow the meter's internal fuse.
03
Test a Known Live Circuit
Before relying on a "no voltage" reading, verify your meter is working by testing a known energized outlet or circuit. This confirms batteries are good and probes are making contact. Never trust a meter that hasn't been verified.
04
Position Probes for Measurement
For voltage, touch one probe to each point being measured. Line-to-line voltage requires probes on both hot conductors. Line-to-ground requires one probe on hot, one on ground or neutral. Maintain firm contact until reading stabilizes.
05
Read and Record
Note the voltage displayed. For AC circuits, the meter shows RMS (root mean square) voltage. Record measurements for comparison with specifications. Voltage more than 10% above or below rated values indicates problems with power supply or wiring.
Using Your Clamp Meter: Amperage Testing
Step-by-Step Procedure
Set up your clamp meter: Turn the dial to AC amperage mode (A~). Open the clamp jaws using the trigger or lever. The jaws must fully open to fit around conductors without damage.
Isolate a single conductor: Clamp around ONE wire only—never clamp around multiple wires in a cable. Current flowing opposite directions cancels out, giving zero reading. For multi-wire cables, you may need to separate wires at a junction box or peel back insulation to access a single conductor.
Take your reading: Close the jaws completely around the wire. The meter displays current in amps. Compare to equipment nameplate for rated load amperage (RLA). Running amperage should be within 10% of RLA. Higher readings indicate problems like dirty filters, low refrigerant, or bearing failure.
Interpreting Amp Readings
Compressor starting amps (locked rotor amps or LRA) are 4-6 times higher than running amps for the first second. Most clamp meters don't capture this. Use in-rush mode if available.
Low amperage suggests loss of load—perhaps a slipping belt, failed capacitor reducing motor speed, or loss of refrigerant charge in a compressor circuit.
High amperage indicates the motor is working too hard. Check for restricted airflow, bad bearings, low voltage, or single-phasing in three-phase equipment.
Understanding Electrical Measurements
Voltage (Volts)
Electrical pressure or potential difference between two points. Like water pressure in a pipe, voltage is the force pushing electrons through a circuit. Higher voltage can move more current through a given resistance. Standard HVAC voltages: 24V control circuits, 120V accessories, 240V residential power, 480V commercial power.
Current (Amps)
The rate of electron flow through a conductor, analogous to water flow rate measured in gallons per minute. One ampere equals one coulomb of charge (6.24×10^18 electrons) passing a point per second. High current requires larger wire to prevent overheating. Equipment amperage determines proper wire size, breaker size, and disconnect rating.
Resistance (Ohms)
Opposition to current flow. Like friction in a water pipe, resistance converts electrical energy to heat. Conductors have low resistance (copper wire: 0.001 ohms per foot). Insulators have high resistance (rubber: millions of ohms). Components like heater elements have designed resistance values. Opens have infinite resistance. Shorts have zero resistance.
Power (Watts)
The rate of energy consumption or work performed. Calculated as Voltage × Amperage (W = V × A). A 240V compressor drawing 20A consumes 4,800 watts or 4.8 kilowatts. Electric bills charge for kilowatt-hours (kWh)—running that compressor for one hour uses 4.8 kWh. Understanding power helps size generators and calculate operating costs.
Ohm's Law: The Foundation of Electrical Understanding
The Basic Formula
E = I × R
E = Voltage (Electromotive force) in Volts
I = Current (Intensity) in Amperes
R = Resistance in Ohms

This simple equation relates the three fundamental electrical quantities. Knowing any two values allows you to calculate the third. Rearrange the formula as needed: I = E/R or R = E/I
Practical Applications
Example 1: A 240V heater element draws 15 amps. What is its resistance? Using R = E/I: R = 240V / 15A = 16 ohms. You can verify this by measuring the element's resistance with your ohmmeter.
Example 2: A 24V control circuit has a resistance of 48 ohms (relay coil plus wire resistance). How much current flows? Using I = E/R: I = 24V / 48Ω = 0.5 amps or 500 milliamps. This helps size transformers and fuses.
Example 3: A wire run has 0.5 ohms of resistance and carries 20 amps. What is the voltage drop? Using E = I × R: E = 20A × 0.5Ω = 10 volts lost in the wire. If the supply is 240V, only 230V reaches the equipment—a 4.2% drop.
Ohm's Law applies to DC circuits directly and AC circuits if resistance is the only opposition (no inductance or capacitance). For AC motors, impedance (Z) replaces simple resistance, but the concept remains the same.
Safety Devices: Circuit Protection
Fuses
Single-use protection devices containing a thin metal strip that melts when current exceeds the rated value, opening the circuit instantly. Low-voltage control circuits typically use 3-5 amp fuses. Time-delay fuses withstand brief motor starting surges. Always replace with the same amp rating—oversizing defeats the protection and can cause fires.
Circuit Breakers
Reusable protection devices using electromagnetic or thermal mechanisms to trip and open the circuit when overloaded. Unlike fuses, breakers can be reset after the fault is cleared. Magnetic breakers respond instantly to shorts. Thermal breakers trip on sustained overcurrent. Combo breakers provide both types of protection for comprehensive safety.
Disconnects
Mechanical switches that completely isolate equipment from power, required within sight of outdoor units per electrical code. Pull-out disconnects use removable fuse blocks. Lever disconnects have external handles. Both create a visible gap in the power circuit. Lockout/tagout devices attach to disconnects to prevent accidental re-energization during service work.
Capacitors: Energy Storage in Electrical Circuits
What Capacitors Do
Capacitors store electrical energy in an electric field between two conductive plates separated by an insulator (dielectric). In HVAC systems, capacitors serve two main purposes: helping motors start (start capacitors) and improving motor efficiency while running (run capacitors).
Start capacitors provide a phase shift that creates a rotating magnetic field, giving the motor a powerful starting torque. They're designed for short-term use (less than one second) and disconnect via a centrifugal switch once the motor reaches speed. Rated in microfarads (µF), typically 50-500µF.
Run capacitors remain in the circuit continuously, improving power factor and motor efficiency. They reduce current draw by 10-30% and help motors run cooler. Run capacitors are oil-filled metal cans rated for continuous duty, typically 5-80µF. They're polarized and must be installed correctly.
Testing and Replacing Capacitors
Bad capacitors are a leading cause of HVAC failures. Symptoms include motors that won't start, hum loudly, or run hot. Bulging, leaking, or burned capacitors should be replaced immediately.
Testing procedure: Disconnect power and discharge the capacitor using an insulated screwdriver across terminals. Set your capacitor tester to the correct range and connect leads to the capacitor terminals. The reading should match the label rating within ±6% for run capacitors and ±20% for start capacitors.
Replacement guidelines: Always replace with same or higher voltage rating. Microfarad rating should match within 10% for run capacitors—too high or low affects motor performance. Match or exceed temperature ratings. Dual capacitors combine run capacitors for compressor and fan in one can with shared common terminal.
Lab Exercise: Hands-On Electrical Work
Today's lab gives you practical experience with the electrical concepts covered this week. You'll work in pairs on training benches equipped with real HVAC components. This controlled environment lets you make mistakes safely while building the muscle memory and confidence needed for field work.
Part 1: Wire a Thermostat to a Trainer Board
Your bench has a board with a 24V transformer, relay coils, indicator lights, and terminal blocks. Connect a thermostat using proper wire colors and techniques. When your thermostat calls for cooling, the yellow light should illuminate. When calling for heat, the white light should turn on.
Skills practiced: Wire stripping, terminal connections, wire routing, voltage verification. Your instructor will check your work before energizing the circuit. Troubleshoot any wiring errors using your multimeter.
Part 2: Test Voltage at Multiple Points
Using your multimeter, measure and record voltages at specific test points throughout the circuit. Measure transformer primary (120V), transformer secondary (24V), voltage at the thermostat R terminal, voltage at the relay coil when thermostat is calling for cooling, and voltage drop across wire runs.
Skills practiced: Safe meter usage, probe placement, reading and interpreting voltage measurements. Document your findings on the lab worksheet. Compare results with your partner to verify accuracy.
Part 3: Measure Current Draw with Clamp Meter
The training boards include a motor on a variable load. Using your clamp meter, measure current draw at no load, medium load, and full load. Record amperage at each setting. Observe how current increases as mechanical load increases.
Skills practiced: Clamp meter operation, isolating single conductors, interpreting amperage readings. Calculate power consumption (watts) at each load level using Ohm's Law. Discuss with your partner how this relates to compressor operation in actual systems.
Lab Exercise Continued: Advanced Testing
Part 4: Test Capacitors
Your workbench has several capacitors—some good, some defective. Using your capacitor tester, measure each one and record the µF reading. Compare against the labeled rating. Identify which capacitors are within spec and which should be condemned. Visual inspection: examine for bulging, leaking, or burn marks. These are automatic fails even if they test okay.
Part 5: Identify Wiring Diagram Symbols
Study the wiring diagram provided for a residential air conditioning system. On your worksheet, identify each component: transformer, contactor, capacitor, compressor, fan motor, thermostat, and high-pressure switch. Trace the 24V control circuit from R terminal through the thermostat to the contactor coil. Trace the 240V power circuit from the disconnect through the contactor to the compressor.
Part 6: Troubleshoot a Simulated Fault
Your instructor has introduced a fault into your training circuit. Using only your meters and systematic diagnostic procedures, identify the problem. Start with visual inspection, then test voltages at key points. Check for opens, shorts, and component failures. Document your troubleshooting process—what you tested, what you found, and how you reached your conclusion. This is essential field diagnostic practice.
Lab Safety Reminders

Before You Begin
  • Put on safety glasses—mandatory at all times in the lab
  • Remove all jewelry, watches, and conductive accessories
  • Verify your multimeter and clamp meter have fresh batteries
  • Inspect all tools for damage—report any issues to instructor
  • Never work on energized circuits without instructor supervision
  • Always discharge capacitors before touching terminals

🦆 The Daycool Way
"Measure twice, energize once." This lab mirrors real-world service calls. The habits you develop here become automatic in the field. Take your time, follow procedures exactly, and ask questions whenever you're uncertain.
Professional technicians stay safe by respecting electricity, using proper tools, and following systematic processes. These aren't just lab rules—they're the foundation of a long, successful career in HVAC.
Weekly Knowledge Check Quiz
Time to test your understanding of this week's electrical and control concepts. This quiz covers safety procedures, circuit fundamentals, thermostat operation, and diagnostic techniques. Answer all questions independently before checking with your instructor. Passing score is 80% or higher.
1
Explain the purpose of lockout/tagout procedures and list the six steps.
2
A 240V circuit draws 18 amps. Using Ohm's Law, calculate the circuit resistance.
3
What is the difference between a start capacitor and a run capacitor? When is each used?
4
Describe how a contactor works. What voltage typically controls it, and what voltage does it switch?
5
A thermostat's Y terminal connects to which equipment component? What happens when this circuit energizes?
6
Why is a C-wire necessary for SmartFeather thermostats but not for older mechanical thermostats?
7
List four common thermostat wiring mistakes and how to avoid them.
8
What three measurements can a multimeter perform? Give an example of when you'd use each in HVAC work.
Quiz Questions Continued
1
A compressor nameplate lists RLA of 22 amps. You measure 27 amps with your clamp meter. What might this indicate?
2
Describe the proper procedure for using a clamp meter to measure compressor amperage.
3
What is voltage drop? What percentage is acceptable in HVAC circuits? How do you reduce it?
4
A run capacitor tests at 32µF but the label reads 40µF. Should it be replaced? Why or why not?
5
What safety equipment must you wear when working with high-voltage electrical systems?
6
Explain the difference between a ladder diagram and a pictorial diagram. When would you use each?
7
Name three features of the SmartFeather thermostat that customers value and explain why.
Real-World Scenario: Troubleshooting Challenge
The Service Call
You arrive at a residential service call. The customer reports their air conditioner stopped working last night. Outside temperature is 92°F and climbing. Here's what you observe:
  • Thermostat is set to 72°F in cooling mode
  • Display shows the system is calling for cooling
  • Indoor blower is running normally
  • Outdoor unit is completely silent—no compressor or fan
  • No unusual smells or visible damage
The homeowner mentions they heard a "click" but nothing else when the AC tried to start. How would you systematically diagnose this problem?
Your Diagnostic Process
  1. Safety first: What's your initial safety procedure before opening any panels?
  1. Visual inspection: What would you look for on the outdoor unit?
  1. Voltage testing: Where would you measure voltage and what readings would you expect?
  1. Component testing: Which components would you test and in what order?
  1. Most likely cause: Based on symptoms, what's the probable failure?
Discuss your approach with your group. Compare diagnostic strategies. Remember: systematic procedures prevent missed clues and unnecessary part replacements.
Scenario Solution and Learning Points
Let's walk through the professional diagnostic approach for the silent outdoor unit scenario. This systematic process applies to countless service calls you'll encounter.
1
Verify the Complaint
Confirm the thermostat is calling for cooling and the indoor blower responds. The customer heard a "click"—likely the contactor attempting to close. This click is a critical clue suggesting the control circuit is working but something is preventing the contactor from pulling in fully or staying closed.
2
Check Power at the Disconnect
Test voltage at the outdoor disconnect. You should read 240V line-to-line. If you have proper voltage here but the unit isn't running, the problem is between the disconnect and the equipment or within the unit itself. No voltage here points to a tripped breaker or wiring problem upstream.
3
Test Control Voltage at Contactor
Check 24V at the contactor coil terminals when thermostat is calling for cooling. Proper control voltage confirms the transformer, wiring, and thermostat are functioning. No voltage suggests a control circuit problem—broken wire, bad transformer, or thermostat failure.
4
Inspect and Test the Contactor
With 24V present at the coil but contacts not closing, the contactor has likely failed mechanically. Possible causes: burned coil, seized armature, welded or pitted contacts from previous short circuit. Test coil resistance (should be 50-200 ohms). Replace the contactor—it's the most common failure point matching these symptoms.

Key takeaway: Following a logical sequence from power source to load prevents guessing and unnecessary part replacements. Document your voltage readings at each test point. This systematic approach becomes second nature with practice.
Week 5 Wrap-Up: What You've Mastered
Core Competencies Achieved
You've completed intensive training in electrical systems and controls—arguably the most technical aspect of HVAC work. You now understand what happens when a customer adjusts their thermostat and how electrical energy flows through control and power circuits to create comfort.
Safety consciousness is now part of your DNA. You can implement proper lockout/tagout procedures, test for voltage before touching circuits, and recognize electrical hazards before they cause injury.
Diagnostic skills separate professional technicians from parts changers. You can read wiring diagrams, trace circuits logically, use test equipment correctly, and follow systematic troubleshooting procedures to identify root causes.
Practical Skills Developed
Installation expertise includes proper wire sizing, correct terminal connections, thermostat configuration, and system testing procedures. You can install a SmartFeather thermostat correctly the first time and explain its features to customers confidently.
Tool proficiency with multimeters, clamp meters, and capacitor testers allows you to measure and verify electrical values accurately. You understand what readings indicate and how they relate to system operation.
Component knowledge covers transformers, contactors, capacitors, thermostats, and safety devices. You know how each component functions, common failure modes, and proper testing procedures.
Preparing for Next Week: Troubleshooting Deep Dive
Week 6 builds directly on your electrical knowledge by teaching systematic troubleshooting methodology. You'll learn to diagnose complex problems efficiently, reducing callbacks and increasing customer satisfaction.
Advanced Diagnostics
Move beyond basic testing to understand system operation at a deeper level. Learn to identify patterns in symptoms, use diagnostic flowcharts effectively, and develop troubleshooting intuition through case studies of real-world failures. Focus on efficiency—solving problems in 30 minutes instead of 3 hours.
Refrigeration Cycle Troubleshooting
Connect pressure and temperature readings to electrical measurements for complete system analysis. Understand how mechanical problems create electrical symptoms and vice versa. Learn when a system needs refrigerant, when it needs electrical repair, and when both issues coexist.
Customer Communication
Technical knowledge means nothing if you can't explain problems clearly to non-technical customers. Practice translating diagnostic findings into plain language, presenting repair options fairly, and building trust that leads to long-term customer relationships and referrals.
Study Guide and Additional Resources
1
Review Your Lab Worksheets
The hands-on exercises completed this week contain valuable reference information. Review your voltage measurements, circuit diagrams, and troubleshooting notes. Compare your results with classmates to identify any gaps in understanding.
2
Practice Reading Wiring Diagrams
Equipment manufacturers publish wiring diagrams online. Download diagrams for common residential units and practice tracing circuits. Start with simple single-stage cooling systems, then progress to heat pumps with auxiliary heat, and finally multi-stage commercial units.
3
Watch Electrical Safety Videos
The Daycool training portal includes video demonstrations of proper lockout/tagout procedures, meter usage, and capacitor testing. Watch these at least twice—once for the overview, once for the details you might have missed initially.
4
Study SmartFeather Installation Manual
Read the complete SmartFeather installation guide available in your training materials. Pay special attention to compatibility charts, C-wire solutions, and WiFi setup procedures. You'll be expected to confidently recommend and install these systems.
5
Review Quiz Questions
Retake today's quiz without looking at notes. If you score below 90%, identify weak areas and study those topics specifically. Electrical fundamentals are too important for gaps in knowledge—they affect everything you'll do in this career.
Stay Cool with Daycool: You're Becoming a Pro!
Week 5 Complete! 🦆
You've conquered electrical systems and controls—one of the most challenging aspects of HVAC training. The safety procedures, diagnostic skills, and technical knowledge you've gained this week form the foundation for advanced troubleshooting.
Your progress:
  • ✓ Week 1: HVAC Fundamentals
  • ✓ Week 2: Tools & Safety
  • ✓ Week 3: Airflow Systems
  • ✓ Week 4: Refrigeration Cycle
  • ✓ Week 5: Electrical & Controls
  • → Week 6: Troubleshooting
  • → Week 7: Installation Best Practices
  • → Week 8: Customer Service Excellence
Mindset for Success
Professional HVAC technicians respect electricity without fearing it. You now have the knowledge and skills to work safely and effectively with electrical systems. Continue building confidence through practice, asking questions, and learning from experienced technicians.
Remember the Daycool standard: Every wire connection matters. Every voltage reading tells a story. Every safety procedure exists for a reason. The attention to detail you bring to electrical work directly impacts customer safety, system reliability, and your professional reputation.
See you Monday for Week 6, where we put everything together and learn to diagnose problems like master technicians. Get some rest—you've earned it!

Questions or need extra help? Contact your instructor or visit the Daycool Academy support center. We're here to ensure your success.